I-GD3128 Series Insulation Resistance Tester
I-GD3128 yochungechunge lwe-Insulation Resistance Tester inomsebenzi ophelele wokuhlola wamapharamitha ahlukahlukene wokumelana nokufakwa kanye nekhono elihle kakhulu lokulwa nokuphazamiseka, elingasetshenziswa ukuhlola ukumelana nokufakwa kwamthamo omkhulu wezinto zikagesi zamandla kagesi aphezulu kanye nemigqa yokudlulisela endaweni eqinile yokungenisa inductive njengesiteshi esincane.Ithuluzi lamukela isikrini esithintwayo sombala wangempela, yonke idatha yokuhlola namandla ebhethri kuboniswa esikrinini esifanayo ngokubuka nje, futhi inhlanganisela yokushintsha kweknobhu nokhiye kwenza umsebenzi ube lula kakhulu.Umsebenzisi akadingi ukubamba ngekhanda indlela yokusebenza.Chofoza u-"SIZO" esikrinini ukuze uveze indlela yokusebenza, engaqondisa ngempumelelo umsebenzisi ukuthi asebenzise ithuluzi.Ithuluzi linomsebenzi wokukhipha ngokushesha, okungakhipha i-voltage yento ehloliwe ngokushesha ngaphandle kwesekethe yokukhipha eyengeziwe.I-voltage monitor yensimbi ingagada ngokuzenzakalela i-voltage ebukhoma yento ehloliwe.Uma i-voltage idlula i-36V, ukuhlolwa kuzovinjelwa ngokuzenzakalelayo, okungavikela ngempumelelo ithuluzi kanye nabaqhubi.
Ithuluzi lamukela umthamo omkhulu webhethri we-lithium ongashajwayo.Isibali sikhathi sokuhlola ithuluzi sirekhoda ngokuzenzakalelayo isikhathi sokuhlola futhi sigcine imiphumela yokuhlolwa nosuku nesikhathi.Isikrini sokuthinta singafinyelela kalula kudatha yomlando erekhodiwe.Isixhumi esibonakalayo se-USB esihlukaniswe ngokuphelele singalayisha ngokuphephile idatha yokuhlola ku-PC.Ithuluzi lifakwe ulayini wokuhlola one-insulation ephindwe kabili kanye nesendlalelo esivikelayo, futhi ibha kagesi ephezulu ifakwe isiqeshana sengwenya eshintshwayo nehhuku, engajwayelana nezindawo zokuhlola ezahlukahlukene.Ithuluzi lamukela ukwakheka kwegobolondo eliqinile elinezendlalelo ezimbili, futhi izinga lokuvikela lebhokisi langaphandle yi-IP65, elingavimbela ukuhlasela komswakama nothuli ngesikhathi sokuthutha nokugcinwa, futhi livikele ngempumelelo ithuluzi ekungqubuzaneni.
Uchungechunge lwe-GD3128 lunobubanzi obubanzi, ukulungiswa okuphezulu, ukusebenza okulula, ukuqina nokuqina, ukunemba nokuthembeka, ukusebenza okuzinzile, nekhono eliqinile lokulwa nokuphazamiseka.Ithuluzi linokuhlolwa kokumelana nokushisa (IR);ukuhlolwa kwenkomba ye-polarization (PI);ukuhlolwa kwesilinganiso sokumuncwa (i-DAR);ukuhlolwa kwe-ramp (RAMP);ukuhlolwa kwesihlungi (FR, 10S, 20S, 30S, 40S izinketho ezine);ukuhlolwa kwamandla kagesi (V);ukuhlolwa kwamandla (uF);ukuhlolwa kwamanje (nA) neminye imisebenzi.Ithuluzi lifanele ukuhlolwa kokumelana nokufakwa kwemishini kagesi, izintambo zokudlulisela kanye nezinye izinto zokusebenza ezinkulu ngaphansi kwemvelo yomthamo omkhulu, i-voltage ephezulu kanye nokungeniswa okunamandla.Kuyithuluzi elisetshenziswa kakhulu futhi elibalulekile lamandla kagesi, ezokuxhumana, isimo sezulu, igumbi lekhompyutha, indawo kawoyela, ukufakwa nokugcinwa kwe-electromechanical, kanye neminyango yokuphakelwa kukagesi yezimboni nezimayini.
●Isilinganiso esiphezulu se-short-circuit current ngu-7mA.
●Ukuhlolwa kokumelana ne-Insulation (IR), ukuhlolwa kwenkomba ye-polarization (PI), ukuhlolwa kwesilinganiso sokumuncwa (i-DAR).
●Imodi yokuhlola i-Ramp (RAMP), imodi yokuhlola isihlungi (FR), ukuhlolwa kwe-capacitance (uF)
●Voltage qapha umsebenzi, ukuqapha ngokuzenzakalelayo voltage voltage into ihlolwe.
●Umsebenzi wokuhlola isikhathi, qopha ngokuzenzakalelayo isikhathi sokuhlola.
●Umsebenzi wokukhipha okuzenzakalelayo, ngokuzenzakalelayo futhi ukhulule ngokushesha ukushajwa kwento yokuhlola ngemva kokuhlolwa, ngaphandle kwesifunda sokukhishwa kwangaphandle.
●Umsebenzi wokuvala shaqa okuzenzakalelayo.
●Isikrini esikhulu sombala wokuthinta.
●Ukwakheka kwegobolondo elendlalelo ezimbili, liqinile futhi liqinile, izinga lokuvikela i-IP65.
●Iphakethe lebhethri le-lithium elikwazi ukushajwa kabusha.
●Umsebenzi wesitoreji, ungagcina ngokuzenzakalelayo amaqembu ayi-1000 edatha yokuhlola yesikhathi sangempela nedethi yokuhlola nesikhathi nesikhathi sokuhlola.
●Layisha umsebenzi, ifakwe USB interface, irekhodi idatha ingalayishwa kukhompyutha ukuze kuhlaziywe izibalo idatha.
Imodeli Yomkhiqizo | I-Voltage elinganiselwe | I-Insulation Resistance Range | Isifunda Esifushane Samanje |
GD3128A | 250V,500V,1kV,2.5kV,5kV | 0.50MΩ~10.0TΩ | ≥7mA |
I-GD3128B | 250V,500V,1kV,2.5kV,5kV,10kV | 0.50MΩ~20.0TΩ | ≥7mA |
I-GD3128C | 250V,500V,1kV,2.5kV,5kV,10kV,15kV | 0.50MΩ~30.0TΩ | ≥7mA |
I-Insulation Resistance Range kanye nokunemba
I-Voltage elinganiselwe | I-Insulation Resistance Rage | Ukunemba | Phawula |
250V | 0.50MΩ~50.0GΩ | ±5%rdg±3dgt |
|
50.0GΩ~500GΩ | ±20%rdg±3dgt |
| |
500V | 1.00MΩ~100GΩ | ±5%rdg±3dgt |
|
100GΩ~1.00TΩ | ±20%rdg±3dgt |
| |
1000V | 1.00MΩ~200GΩ | ±5%rdg±3dgt |
|
200GΩ~2.00TΩ | ±20%rdg±3dgt |
| |
2500V | 1.00MΩ~500GΩ | ±5%rdg±3dgt |
|
500GΩ~3.00TΩ | ±20%rdg±3dgt |
| |
5000V | 1.00MΩ~1.00TΩ | ±5%rdg±3dgt |
|
1.00TΩ~10.0TΩ | ±20%rdg±3dgt |
| |
10KV | 1.00MΩ~2.00TΩ | ±5%rdg±3dgt |
|
2.00TΩ~20.0TΩ | ±20%rdg±3dgt |
| |
15kV | 1.00MΩ~3.00TΩ | ±5%rdg±3dgt |
|
3.00TΩ~30.0TΩ | ±20%rdg±3dgt |
1 TΩ (Tera ohm)=1000GΩ=1012Ω
1 GΩ (Giga ohm)=1000MΩ=109Ω
1 MΩ (Mega ohm)=1000KΩ=106Ω
Umsebenzi | Isilinganiso sokumelana ne-insulation (IR);i-polarization index measurement (PI);ukumuncwa isilinganiso (DAR);Imodi yokuhlola i-ramp (RAMP);isihlungiumsebenzi(10S, 20S, 30S, 40S);visilinganiso se-oltage(V);amandlai-tanceukulinganisa(uF);isilinganiso samanje(nA) |
Ukunikezwa kwamandla kagesi | Ibhethri le-lithium elingashajwa kabusha 6.2Ah |
I-Voltage elinganiselwe | GD3128A: 250V, 500V, 1kV, 2.5kV, 5kV I-GD3128B: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV I-GD3128C: 250V, 500V, 1kV, 2.5kV, 5kV, 10kV, 15kV |
Ukunemba kwe-Voltage Output | (5%~10%) ±10V |
Ibanga Lokuhlola Ukumelana Ne-Insulation | GD3128: 0.50MΩ~10.0TΩ I-GD3128B: 0.50MΩ~20.0TΩ I-GD3128C: 0.50MΩ~30.0TΩ |
Okukhiphayo Kwesekethe Emfishane Yamanje | ≥7mA |
I-Polarization Index Test | Yebo |
Ukuhlolwa kwe-Absorption Ratio | Yebo |
I-Ramp Test Mode | Hlola ngezinyathelo ezingu-10% we-voltage esethiwe kuze kufike i-voltage esethiwe. |
Imodi Yokuhlola Isihlungi | 10S, 20S, 30S, 40S ukukhetha okune. |
Ukuhlolwa kwe-Voltage | Ibanga: I-AC/DC: 0V~1000V; Ukunemba: ±5%rdg±3V |
Ukuhlolwa Kwekhono | Ibanga: 10nF~25uF; Ukunemba: ±10%rdg±10nF |
Ukuhlolwa Kwamanje | Ibanga: 0.01nA~7mA; Ukunemba: ±5%rdg±0.5nA |
I-Voltage Monitor | Gada i-voltage yetested into, futhi iqaphe isimo sokukhishwa ngemva kokuhlolwa, inqatshelwe ukuhlola lapho i-voltage idlula u-36V, vikela ithuluzi kanye no-opharetha. |
Hlola Isikhathi | Isikhathi sokuhlola okuzenzakalelayo, isikhathiingububanzi: 0s~9999s |
Umsebenzi Wesitoreji | Gcina ngokuzenzakalelayo idatha yokuhlola nedethi yokuhlola nesikhathi, inani lamaqembu angu-1000 |
Layisha Umsebenzi | Layisha idatha egciniwe kukhompuyutha ngentambo yokuxhumana ye-USB. |
Isibonisi Samandla Ebhethri | Ngokuboniswa kwamandla ebhethri, lapho i-voltage yebhethri iphansi izokhumbuzakhokhisaibhethri. |
Ukuvala shaqa okuzenzakalelayo | Ngemuva kwemizuzu eyi-15 ukuqala kuzocisha ngokuzenzakalelayo ngaphandle kokusebenza. |
Ubukhulu | 280mm×260mm×160mm |
Isisindo | 4900g (faka nebhethri) |
Izintambo zokuhlola | Umbala obomvu wentambo yokuhlola i-voltage ephezulu engu-1pc (enea Isiqeshana se-alligator nehhuku), ucingo lokuhlola umbala oluhlaza 1pc, intambo yokuhlola umbala omnyama 1pc |
Izinga Lokuvikela | Vala ikesi IP65, vula ikesi IP40 |
Indawo Yokusebenzela | -20 ℃~50℃; 80%rh |
Imvelo Yesitolo | -25 ℃~65℃; 80%rh |
I-Insulation Resistance | 50MΩ(1000V) (phakathi kwesekethe yokuhlola kanye negobolondo) |
Ukumelana ne-Voltage | AC 3kV50Hz 1 iminithi(phakathi kwesekethe yokuhlola kanye negobolondo) |
Ukuphepha | I-IEC61010-1, I-IEC61326-1 |