I-GDJB-6000D Uhlelo Lokuhlola Ukuvikelwa Kwesiteshi Esingaphansi Esihlakaniphile
I-GDJB-6000D ifakwe isikhulisi samandla okusebenza okuphezulu futhi sisekelwe kuplathifomu enamandla ye-PowerPC+X86.Yamukela umklamo we-modular futhi ibe nemisebenzi enamandla, ukunemba okuphezulu, usayizi omncane kanye nezici zesisindo esincane.Ingahlola ukusebenza nokusebenza kweyunithi yokuhlanganisa, idivayisi yokuvikela idluliselwe, idivayisi yokulinganisa nokulawula, amatheminali ahlakaniphile njll. Ilungele kakhulu izimboni zamandla, iziteshi ezincane, amayunithi ocwaningo lwesayensi ahlukahlukene kanye namabhizinisi okukhiqiza imishini.
●I-Smart Test Module
Ukuhlela isifanekiso sokuhlola okuhlakaniphile kuyasekelwa.Izinto zokuhlola zingangezwa ngokungahleliwe phakathi nenqubo yokuhlola futhi zilondolozwe njengamafayela ephrojekthi okuhlola asebenziseka kabusha ukuze kuthuthukiswe ukusebenza kahle kokuhlola esigabeni sokugcina sokuhlolwa nokuqedwa.
●Ukuhlola okuzenzakalelayo
Ngokuvikelwa kwesayithi kanye nomsebenzi wokuhlola ozenzakalelayo wokuvikelwa kwedijithali, zonke izinto zokuhlola zedivayisi eyodwa yokuvikela zingaqedelwa ngokhiye owodwa.
●Izindlela zokuskena eziningi
Isekela i-amplitude, isigaba, imvamisa, i-impedance, i-vector, ukulandelana, namandla enziwa ngokuhlolwa okwenziwa ngesandla noma okuzenzakalelayo, futhi isekela ukuhlolwa kokushintsha okuzenzakalelayo ngokuya kwendlela yokugreda, ukushelela kanye nokuhlanganiswa.
●Isibonisi sesithombe setheminali ebonakalayo
Sekela umsebenzi wokubonisa umfanekiso wesiphetho esibonakalayo, ukugeleza kwedatha kucacile.
●Thumela futhi wamukele imilayezo ngesikhathi esifanayo
Sekela i-IEC61850-9-1, IEC61850-9-2 kanye ne-GOOSE optical digital message output.Isiginali ye-GOOSE ingathunyelwa futhi yamukelwe ngokuzimela, futhi ingathumela futhi yamukelwe ngesixhumi esibonakalayo se-Ethernet esine-IEC 61850-9-2.
●I-FT3/I-FT3 Enwetshiwe
Isekela i-FT3, i-FT3 yokunwetshwa kanye nokukhishwa komlayezo we-DL/T 282, futhi isekela 2M/4M/6M/8M/10M isilinganiso se-baud se-UART nombhalo wekhodi ongu-5M/10M/20M we-Manchester.
●Ukuhlolwa okungavamile
Ngomsebenzi wokungajwayelekile womlayezo we-analog, ingakwazi ukulingisa okungavamile ngekhwalithi, ukuthumela i-jitter yefrikhwensi, ukubambezeleka okudidayo, ukulahleka kwephakethe, ukuphuma esinyathelweni, ukweqa inombolo ye-serial, imodi yokunakekela, uguquko olubonakalayo lwesimo nokunye ukuhlola.
●Ukudlala iphutha
Isekela ukulingisa iphutha kanye nomsebenzi wokudlala idatha wefomethi ye-COMTRADE.
●Isevisi ye-MMS
Ngomsebenzi wokufunda nokubhala we-MMS, ingafunda futhi ibhale izilungiselelo zemishini ye-IED ehlakaniphile nolunye ulwazi lokumisa.
●Ukuvumelanisa isikhathi nokunikeza isikhathi
Ngomsebenzi wokucupha ovumelanisiwe, usekelo lokufinyelela okuqondile ku-antenna ye-GPS/BD ngesikhathi sokuvumelanisa, futhi isekela imodi yesikhathi ye-IRIG-B, PPS kanye ne-PTP 1588 futhi ingasekela ukuphuma kwangaphandle kwe-IRIG-B, PPS kanye ne-PTP 1588 enikeza isignali isikhathi.
●Okokufaka kanambambili othintana kanzima kanye nokuphumayo kanambambili
Amanani okokufaka ayasebenza futhi othintana nabo abaguquguqukayo abakhona, futhi uhlobo lokufakwayo ne-voltage yokufaka zibonwa ngokuzenzakalelayo.Amashaneli ahlukanisiwe komunye nomunye, futhi uxhumano lwe-polarity luhlehla ngokwaziswa kwe-alamu.
●Ukwamukela nokuhlaziya umlayezo
Ngomsebenzi wokwamukela nokuhlaziya umlayezo, umlayezo owamukelwe ungavulwa nge-ZHNPA ukuze uhlaziywe noma uthunyelwe.
●Imodi yefiber eyodwa
Imbobo yokubona isekela ukudluliswa kwefayibha eyodwa kanye nokwamukela kwefayibha eyodwa futhi isekela ukuhlolwa kwamandla okubona.
●Isignali encane ye-analog
Ifakwe isibonisi esibonakalayo esincane se-analog, isekela indlela engu-12 yokufaka isignali encane ye-analog, ingakala -7V~ 7V AC voltage, isekele indlela engu-12 yokuphuma kwesignali encane ye-analog, futhi ingakhipha -7V~ 7V AC voltage.
●Ukusebenza kokuthinta
Ifakwe isibonisi esinokulungiswa okuphezulu okungu-10.4 inch esisekela ukusebenza kokuthinta.
●Ukuxhumeka okungenantambo
Nikeza umsebenzi wokuhlola wesilawuli kude, ngemojuli ye-WiFi, esebenziseka kalula.
I-IEC 61850 port yokuxhumana | |
Umsebenzi | Noma yikuphi ukucushwa kwe-IEC 61850 9-1/9-2 SMV transmission, ukwamukela noma iGOOSE transmission and reception |
Uhlobo lwesixhumi esibonakalayo | I-LC optical port |
Ubuningi | 8 pair, 6 pairs*100M adaptive, 2 pairs *100/1000M adaptive |
Ubude begagasi | 1310nm |
I-IEC 60044 port yokuxhumana | |
Umsebenzi | GB/T 20840.8, DL/T 282, Q/GDW441 umlayezo owamukelayo nowuthumelayo |
Uhlobo lwesixhumi esibonakalayo | ST |
Ubuningi | 6*ukuthumela isikhombimsebenzisi, 2* ethola isikhombikubona |
Isigaba | |
Ibanga | 0~360° |
Ukunemba | ±0.1° |
Isixazululo | 0.1° |
Imvamisa | |
Ibanga | 0 ~ 1000Hz |
Ukunemba | <±0.001Hz(0~65Hz) <±0.01Hz(65~450Hz) <±0.02Hz(450~1000Hz) |
Isixazululo | 0.001Hz |
Isikhathi | |
Ibanga | 10ms ~9999.999s |
Isixazululo | 1ms |
Okokufaka kothintana naye kanambambili | |
Ubuningi | 8 amapheya, Ingaxhunywa kuukuxhumana okungenzi lutho kanye nokuxhumana okungenzeka (0~250V) |
Okukhiphayo kothintana naye kanambambili | |
Ubuningi | 6 amapheya, 2 amapheya aphuma ngokushesha |
Ukuphula amandla | I-DC250V /0.5A |
Isikhathi sokuphendula | <100us |
Vumelanisa | |
Uhlobo lwesixhumi esibonakalayo | I-GPS/BD ANT;I-IRIG-B/PPS isignali yokubona;I-IRIG-B/PPS isignali kagesi;IEEE 1588 |
Ubuningi | 1*GPS/BD ANT; I-2 * IRIG-B / PPS isignali ye-optical : 1 * ukuvumelanisa isikhathi, 1 * ukunikeza isikhathi; 2 amapheya*IRIG-B/PPS isignali kagesi :1 amapheya *ukuvumelanisa isikhathi, 1 amapheya * isikhathi ukunikeza; 1 amapheya* IEEE 1588 |
Ukuxhumeka okungenantambo | |
Uhlobo lwesixhumi esibonakalayo | I-WIFI |
Uxhumano lwezintambo | |
Uhlobo lwesixhumi esibonakalayo | 100M Lan port, RJ45 |
Ubuningi | 2 izingcezu |
Okokufaka kwesignali encane ye-analogi | |
Uhlobo lwesixhumi esibonakalayo | Ipulaki yendiza, i-AC voltage |
Ubuningi | 12 isiteshi |
I-analog encane ephumayo yesignali | |
Uhlobo lwesixhumi esibonakalayo | Ipulaki yendiza, i-AC voltage |
Ubuningi | 12 isiteshi |
Ukunikezwa kwamandla kagesi | |
Amandla kagesi | AC/DC 220V , Ukuchezuka okuvumelekile: -20%~15% |
Imvamisa | 47 ~ 65Hz |
Isixhumi esibonakalayo se-USB | |
Ubuningi | 2 izingcezu |
Indawo yokusebenza | |
Izinga lokushisa lokusebenza | -10℃~50℃ |
Umswakama | ≤95%,ukungafinyeleli |
Abanye | |
Isisindo | 5.5 kg |
Ubukhulu | 146×390×212mm(L×W×H) |
Isixhumi esibonakalayo esiku-inthanethi | RJ45 |
Bonisa | Isikrini sokuthinta se-LCD esingu-10.4 intshi sangempela |