I-GDKC-12A (GDKC-12B) (GDKC-13A) Isihlaziyi Sesekithali
I-high voltage circuit breaker ingenye yemishini yokulawula ebaluleke kakhulu ohlelweni lwamandla.I-GDKC-12A/B (GDKC-13A) isetshenziselwa ukuhlola izici eziguquguqukayo ze-high voltage circuit breaker.Kulula ukusebenza, ngokunemba okuphezulu.
●Isikhathi: isikhathi esivulekile / sokuvala, ekuvumelaniseni kwesigaba, ukuvumelanisa kwesigaba kuya kwesigaba sabathintana nabo abangu-12.
●I-resistor yokuvala: isikhathi sokushintsha ngaphambi kwesikhathi, i-waveform yokushintsha kwangaphambili kanye nokumelana ne-resistor yokuvala yeziteshi ezingu-6.
●Ukuvala kabusha: vala-vula, vula-vala, vula-vala-isikhathi esivulekile soxhumana naye ngamunye.
●I-Bounce: isikhathi sokugxuma, izikhathi, inqubo kanye ne-waveform yoxhumana nabo ngamunye.
●Isivinini: isivinini lapho thintana khona vula noma vala, isivinini esiphezulu, ijika lesici lokuhamba kwesikhathi;okokuqala vula, okokuqala vala futhi okwesibili isivinini sokuvala kabusha.
●Ukuhamba: uhambo oluphelele, uhambo oluvulekile, uhambo oludlulayo, uhambo oludlulayo, i-bounce amplitude.
●Okwamanje: vula/vala okwamanje, idayagramu ye-waveform yamanje yekhoyili evulekile/yokuvala.
●I-voltage yokusebenza: i-DC30 ~ 300V/20A yedijithali eyakhelwe ngaphakathi, umthombo wamandla olungisekayo we-breaker, qedela ngokuzenzakalelayo ukuhlolwa kwesenzo se-LV se-breaker yesekethe kanye nokulinganisa inani le-voltage yesenzo se-breaker circuit.
●IPC yomsingathi.
●Ifanele ukuhlola amapharamitha wemishini azo zonke izinhlobo ze-SF6 circuit breaker, inhlanganisela ye-GIS kagesi, i-vacuum circuit breaker, i-oil circuit breaker.
●Ikhono eliqinile lokulwa nokuphazamiseka.Ingakwazi futhi ukuhlola kalula futhi ikale ngokunembile ngisho ne-interbus ibukhoma esiteshini esingaphansi esingu-500kV.
●Ngenzwa ye-universal velocity(uyazikhethela), inzwa yesivinini ehambisanayo, inzwa ejikelezayo, kulula ukuyifaka.
●Isenzo sesikhathi esisodwa kuphela sokuthola yonke idatha kanye nefomu legagasi elihambisanayo lokuhlolwa kwendlela yokuphula.
●Idatha yokuhlola isitoreji yamaqembu angu-1000, iwashi lesikhathi sangempela elakhelwe ngaphakathi, elilungele ukulondoloza usuku nesikhathi sokuhlola.
●Isibonisi sesikrini se-LCD, esinokulungiswa kokugqamayo kanye nenkumbulo yokucisha amandla.
●Iphrinta eyakhelwe ngaphakathi, ukuze uthole yonke idatha nomdwebo nganoma yisiphi isikhathi ngokushesha.
●Nge-software yokuphatha ukuhlaziywa kwedatha ye-circuit breaker.Kungaxhunyanwa ne-PC.Imiphumela yokuhlolwa igcinwa ngokuqondile ku-hard disk, futhi iyakwazi ukukhipha ezinhlotsheni ezihlukahlukene zohlobo lwenaliti, i-laser noma amaphrinta e-inkjet ukuze imibiko yokuhlola yokuphrinta, ukwenza ukuhlolwa kwenkundla kube yikhompyutha.
●Ukusebenzisa i-U disk ukulondoloza nokudlulisa idatha ngokuqondile.
●Isofthiwe yokuhlaziya ehambisanayo ihlanganiswa ngokuvumelana nencazelo yokuvula, ukuvala isivinini.Ifanele ukukalwa kwesivinini kunoma yiziphi izinhlobo zokushintshwa.
●Ukusetshenziswa Kwemvelo
Amandla Okokufaka: 220V±10%, 50Hz±10% / GDKC-12B: 230V±10%, 60Hz±10%
Ingcindezi Yomoya: 86-106kpa
Izinga lokushisa: -10-40 ℃
Ukuswakama: ≤80%RH
●Ukusebenza Kokuphepha
Ukumelana Nokushisa>2MΩ
Amandla e-Dielectric: I-Shell ingakwazi ukumelana namandla kagesi kagesi angu-1.5kV ngomzuzu ongu-1 ngaphandle kwe-flashover kanye ne-arcing.
●Amapharamitha ayisisekelo
a.Isikhathi: Ibanga 20000.0ms ukulungiswa 0.01ms
Iphutha 0.1ms ±1dijithi phakathi kuka-2000ms
1ms±1dijithi phakathi kuka-20000ms
I-GDKC-12B Amapharamitha ayisisekelo
a.Isikhathi: Ibanga 20000.0ms ukulungiswa 0.01ms
Iphutha elingu-0.01ms ± idijithi engu-2 phakathi kuka-250ms
0.1ms ± idijithi engu-2 phakathi kuka-2500ms
1ms±2 idijithi phakathi kuka-20000ms
I-GDKC-13A Circuit Breaker AnalyzerAmapharamitha ayisisekelo
Isikhathi: Ibanga 4000.0+6000.0 ms ukulungiswa 0.1ms
Iphutha 0.1ms ± idijithi engu-1 phakathi kuka-100ms
0.1% ± idijithi engu-1 ngaphezu kuka-100ms
Isikhathi esifanayo
b.Isivinini: Ibanga 20.00m/s ukulungiswa 0.01m/s
Iphutha ±0.1m/s±1dijithi phakathi kuka-0-2m/s
±0.2m/s±1 idijithi ngaphezu kuka-2m/s (± 0.2m / s ± idijithi engu-1 ngaphezu kuka-100ms)
c.Ukuvakasha:
Izinhlobo | Ibanga | Isixazululo | Iphutha |
I-vacuum breaker | 50.0mm | 0.1mm | 0.1±1idijithi |
I-SF6 i-circuit breaker | 300.0mm | 1mm | |
AmafuthaI-circuit breaker | 600.0mm |
d.Okwamanje: ububanzi 20.00A ukulungiswa 0.01A
e.Amandla okukhiphayo: DC0-300V digital adjustable / 20A(ukusebenza ngokushesha), isixazululo 1V.
f.Ubukhulu: 360mm (L)* 280mm (W)* 300mm (H)
g.Isisindo: 10kg (9kg)
h.I-GDKC-13A Isisindo: 9kg