I-GMDL-02A HV Circuit Breaker Analog Device
Idivayisi yokulingisa ye-GMDL-02A ye-high-voltage circuit breaker ikhiqizwa kusetshenziswa izimiso zamalungu afanayo amasango ahlelekayo enkambu enkulu, amadivayisi kagesi anamandla anokuvikelwa, njll.
Ikhoyili evulekile iklanywe ngokulandela iluphu ezimele, engalinganisa ukusebenza kwezigaba ezintathu kanye nesigaba sokuhlukaniswa kwezinga le-voltage engu-6-110KV.Ukuziphatha kwesenzo se-single open coil circuit breaker kulungele ukukhethwa kwezinhlelo zamandla, amabhizinisi ezimboni kanye nezimayini, izikhungo zocwaningo lwesayensi, amakolishi ochwepheshe, nabakhiqizi bokuvikela.
Isetshenziswa njengengxenye yama-breaker circuit angempela ekuhlolweni kokudluliselwa kwalo lonke uhlelo lokuvikela ukudluliselwa kanye namadivayisi azenzakalelayo anokushintsha.
Isenzo sinembile, sithembekile, futhi inani lezenzo alikhawulelwe, elingathuthukisa kakhulu ukunemba nokuphelela kokuhlolwa, ukunciphisa inani lezenzo zomephuli wesifunda wangempela, futhi kwandise impilo yesevisi.Kuyithuluzi elibalulekile elisekelayo lomsebenzi wokuhlola ukuvikela i-relay.
Amandla kagesi asebenzayo: | I-AC220V±10% 50HZ yamanje esebenzayo ingaphansi kuka-0.5A | |
I-voltage yokusebenza evulekile futhi evala: | I-DC200V noma i-DC110V. | |
isikhathi sokuvula nesokuvala | ukukhetha isikhathi esivulekile: | Ukuvala isikhathi sokukhetha: |
20ms, 30ms, 40 ms, 50 ms, 60 ms, 70 ms, 90 ms, 110 ms, iphutha alidluli ±5ms | 40 ms, 60 ms, 80 ms, 100 ms, 200 ms, 300 ms, 400 ms, 500 ms, iphutha alidluli ±5ms, (uma 500ms, iphutha lingeqi ±20ms). |
yamanje evulekile futhi evala | vula ukukhetha kwe-resistor: | ∞Ω, 100Ω, 200Ω, 400Ω |
Ukuvala ukukhetha kokumelana: | ∞Ω, 100Ω, 200Ω, 400Ω | |
Umsinga wokuvula nokuvala unqanyulwa ngokuzenzakalelayo ngesikhathi sokuvula nokuvala. | ||
Ukuvula nokuvala ngesandla | Lapho idivayisi yokulingisa i-high-voltage circuit breaker isetshenziswa ngezinkinobho "zokuvala mathupha" kanye "nezinkinobho ezivuliwe ngesandla" kuphaneli, idivayisi yokulingisa i-high-voltage circuit breaker iyavulwa, futhi akukho ukugeleza kwamanje kukhoyili yokuvala. | |
Ukuhluleka kwe-breaker | Uma inkinobho yokuhluleka kwe-circuit breaker icindezelwa, i-circuit breaker ayisebenzi, imisinga yokuvula nokuvala ibambezeleka ngemva kwe-1s bese inqanyulwa, futhi isimo samanje sibuyiselwa ngemva kwamanye ama-20s. | |
Khipha | Khipha: | |
I-DC220V/0.5A, AC220V/5A. | ||
Oxhumana naye ophumayo wesimo se-circuit breaker: | Amapheya angu-12 oxhumana nabo be-circuit breaker position, azimele komunye nomunye.Ihlukaniswe ngamaqembu amabili, ahambelana nekhoyili evulekile ye-circuit breaker. | |
Ukuvala isandla, ukuthintana kweqa ngesandla: | Izinkinobho zokuvala ngesandla kanye nezokugxuma ngesandla ngayinye inomphumela ofanayo ovame ukuvuleka othintana nabo.Uma isandla sivala kanye nezinkinobho zokugxuma ngesandla zicindezelwa, othintana naye uyaxhunywa.Phakathi kwazo, othintana naye ovalwe ngesandla uyazinakekela ngemva kwesenzo, futhi usethwe kabusha ngenkinobho yokweqa ngesandla.Uma inkinobho yokweqa ngesandla ikhishwa, othintana naye weqa uzobuya nokubambezeleka okungu-60ms. |