Ngo-Agasti, ochwepheshe bangemva kokuthengisa be-HV Hipot baya e-Xiangyang.Inhloso yalolu hambo bekuwukuhlinzeka ngezinsizakalo zokususa iphutha likagesi we-Xiangyang Power Supply Company.
Ngemva kokufika endaweni, ngosizo nokubambisana kwekhasimende, ukufakwa kwe-generator ye-voltage impulse voltage kuzokwenziwa.
Ukulungisa iphutha esizeni kwe-GDCY-400kV umbani we-voltage impulse voltage
Ukulinganisa ibanga lebhola elisendaweni: ukulinganisa ibanga lebhola lomzimba kanye nokulinganiswa kwebanga lebhola le-chopper (3000/200/kukalwa)
Ukuhlolwa kokusebenza endaweni: ukuhlolwa okuningi kwe-30KV okuhle nokubi kwe-polarity (hlangabezana ne-T1=1.2±30%/T2=50±20%us/TC=2 ukuya ku-6us)
Ukuhlolwa kwamandla esizeni: i-voltage elinganiselwe ngama-80% okukhiphayo
Ukuqeqeshwa kwethiyori nokusebenza okusendaweni:
Ukuzijwayeza kwekhasimende - ukuhlolwa komkhiqizo okufanisiwe: i-10KV power transformer
1. Ukuhlolwa kwegagasi eligcwele
Izidingo zokuhlola: i-voltage yokuhlola engu-75KV, isikhathi se-waveform T1=1.2±30%/T2=50±20%us
Ukusebenza kwenkundla: usebenzisa i-voltage yezigaba ezimbili
Ukushintshwa kwegagasi kusayithi:
Ukumelana namagagasi ekhanda: 150Ω ezingeni lokuqala, 500Ω ezingeni lesibili (2 1KΩ ngokuhambisana)
Ukumelana nomsila wamagagasi: Isigaba sokuqala esingu-45Ω, isigaba sesibili esingu-45Ω
Ukusebenza kokuhlola kanye ne-waveform:
2. Ukuhlolwa kokunqunywa
Izidingo zokuhlola: i-voltage yokuhlola engu-85KV, isikhathi sekhanda lamagagasi T1=1.2±30%, isikhathi esinqunyiwe TC=2 kuya ku-6us
Ukusebenza kwenkundla: usebenzisa i-voltage yezigaba ezimbili
Ukushintshwa kwegagasi kusayithi:
Ukumelana namagagasi ekhanda: Izinga 1 75Ω, Izinga 2 500Ω (2 1KΩ ngokuhambisana)
Ukumelana nomsila wamagagasi: Isigaba sokuqala esingu-45Ω, isigaba sesibili esingu-45Ω
Ukusebenza kokuhlola kanye ne-waveform:
Ngemva kwalolu chungechunge lokuqeqeshwa, ikhasimende linokuqonda okujulile kwesethi yonke yemishini, okwenza ikhasimende liqiniseke ngokwengeziwe ekusebenzeni kwangempela!
Isikhathi sokuthumela: Aug-24-2022