I-GDSF-411CPD SF6 I-Gas Comprehensive Analyzer
Idatha ye-GDSF-411CPD SF6i-gas comprehensive analyzer iyisisetshenziswa esiphathwayo esiklanyelwe ukukala i-SF6indawo yegesi yamazolo, ukuhlanzeka kanye nomkhiqizo wokubola.Ingxenye eyinhloko enendlela yesibuko esibandayo isetshenziselwa ukuhlola iphuzu lamazolo, inzwa yaseYurophu ngendlela ye-infrared yokuhlola i-SF.6ubumsulwa begesi kanye nenzwa ye-electrochemical kusuka ku-Membrapor ukuhlola i-SF6umkhiqizo wokubola kwegesi.Ngaphandle kwalokho, futhi samukela ama-chips wehadiwe ochwepheshe kanye nama-algorithms wesoftware amahle kakhulu we-STMicroelectronics.
SF6Umswakama
Indlela yokulinganisa | Indlela yesibuko esibandayo (I-Stirling Refrigeration) |
Ibanga lokulinganisa | Iphoyinti lamazolo -100℃--+20℃(ama-90s wokulinganisa iphuzu elilodwa), iphutha: kungcono kuno-±0.2℃ |
Ikhono lokuphinda | ± 0.1 ℃ |
Isixazululo | 0.01℃ |
Iyunithi yokubonisa | ℃, ppm, ℃ P20(inani eliguquliwe ku-20℃) |
SF6Ubumsulwa
Indlela yokulinganisa | Isimiso Sokukala Se-infrared (izinzwa zochungechunge lwe-NDIR) |
Ibanga lokulinganisa | 0 ~ 100% SF6, iphutha: kungcono kuno-± 0.3%FS |
Isikhathi sokuphendula | [90%] 60s |
Ukuphindaphinda | ± 0.3% |
Isixazululo | 0.01% |
Iyunithi yokubonisa | % |
SF6Imikhiqizo yokubola
Indlela yokulinganisa | Isimiso Sezilinganiso Ze-Electrochemical (Izinzwa zochungechunge lwe-Electrochemical kusuka ku-Membrapor) |
Ibanga lokulinganisa | SO2: 0 ~ 200ppmv H2S: 0 ~ 200ppmv CO: 0 ~ 500ppmv HF: 0 ~ 50ppmv |
Ukunemba | SO2: 10ppmv ±3% H2S: 10ppmv ±3% CO: 50ppmv ±4% I-HF: 10ppmv ±3% |
Ikhono lokuphinda | SO2: 10ppmv ±2% H2S: 10ppmv ±2% CO: 50ppmv ±2% I-HF: 10ppmv ±2% |
Isixazululo | 0.01ppmv |
Iyunithi yokubonisa | ppmv |
Amapharamitha ajwayelekile
Ukunikezwa kwamandla kagesi | 220VAC±10%, 50Hz, AC/DC ukusetshenziswa, ukusebenza okuqhubekayo kungaphezu kwamahora angu-8. |
Sebenzisa izinga lokushisa lendawo | -20-+60℃ |
Umswakama wendawo | 90%RH |
Ithonya yenani lokulinganisa | Awukho umphumela wengcindezi nokugeleza |
Ubukhulu | 570*420*280mm |
Isisindo | Hhayi ngaphezu kuka-20 kg. |
Umhloli Omkhulu | 1 isiqephu |
I-adaptha | 1 isethi |
Ipayipi le-Teflon (faka i-valve yokulungisa ukugeleza nesixhumi esisheshayo) | 1 isethi |
Ipayipi lomsila | 1 isethi |
Izingxenye ezisele | 1 isethi |
Ishaja | 1 isiqephu |
Umhlahlandlela Womsebenzisi | 1 isiqephu |
Umbiko Wokuhlola | 1 isiqephu |