I-GDWG-III SF6 Umtshina Wokuvuza Kwegesi
I-GDWG-III SF6umtshina wokuvuza kwegesi, esinobuchwepheshe be-infrared (NDIR) engahlakaziwe, sisetshenziswa kakhulu ukukhomba nokukala ukuvuza kwe-SF6 ku-GIS kanye nezisetshenziswa zokugcwalisa kabusha ngaphakathi kwemboni yamandla.
Izinga lokuvuza lonyaka lezinto zikagesi zegesi ye-SF6 likalwa ngendlela yokubopha.Ngasikhathi sinye, imishini isetshenziswa kabanzi ku-bureau yokuphakelwa kukagesi, iziteshi ezingaphansi, inkampani yokushintsha amandla kagesi aphezulu, indawo yokusebenzela kanye nokuhlolwa kwesayensi.
●I-switchgear ye-voltage ephezulu
●Ama-Helicopter rotor blades
●Isistimu yokudlulisa igesi
●I-fire extinguisher
●Ucwaningo lwezinga lokungena komoya
●Izinto eziyingozi
●Ithangi
●Ayikho ingozi ye-radioactive.
●Asikho isidingo sokushintsha igesi ye-argon yokuhlanzeka okuphezulu njalo.
●Asikho isidingo sokushintsha inzwa njalo, kuyabiza.
●Asikho isidingo sokwenza ukulinganisa komugqa njalo ngonyaka, azikho izingxenye zokugqoka.
●Akwenziwa umswakama, ukungcoliswa kwemvelo noma ukukhukhuleka kwedatha.
●Lapho kukhona ukuvuza okukhulu noma i-SF6ukuhlushwa kwegesi kufika ku-100%, ngeke kungcoliswe noma konakaliswe.
●Ukukala i-SF6ukuvuza kwegesi ngokwekhwalithi nangomthamo.Ukuzwela ku-SF6 igesi 3g/ngonyaka.
●Ukuze uthole i-SF6indawo yokuvuza kwegesi.
●Amapharamitha afana ne-SF6ukugxila kwegesi, izinga lokushisa, umswakama, inkomba yamandla, usuku kanye nesimo sephampu ye-diaphragm kuyaboniswa.
●Isixhumi esibonakalayo esisebenziseka kalula.
●Sebenzisa ubuchwepheshe be-NDIR kanye nenzwa ethuthukisiwe evela eJalimane.
●Isivinini sokuhlola esisheshayo nokuphindaphinda okuhle, idatha iqiniswa phakathi kwama-10s.
●Ngesinxephezelo sokushisa nokucindezela.
●Ayikho i-alamu yamanga, ayikho igesi ngaphandle kwe-SF6izimpendulo.
●Ukulinganisa igesi okungeyena othintwayo kuqinisekisa ukuthi inzwa ngeke ibe nobuthi nganoma isiphi isilinganiso sokuhlushwa.
●Igumbi le-Thermostatic liqinisekisa ukuthi akukho ukukhukhuleka kwezinga lokushisa ezingeni lokushisa elizungezile lenzwa.
●Isibonisi se-OLED esingu-3.5inch, sifundeka ekukhanyeni kwelanga okuqinile.
●Ibhethri le-lithium elakhelwe ngaphakathi, isikhathi sokulinda side.
●Amapayipi enziwe ngokwezifiso ngokwesicelo ngasinye.
●Isampula yokumunca iphampu iqinisekisa ukuvaleka kahle kwendlela yegesi ngaphansi kokuhlolwa.
●Amaqembu angaphezu kuka-100 edatha yokuhlola agcinwa ngokusekelwe ekugxilweni kwegesi kanye nesikhathi sokuhlola, okulula ukukubuza.
●I-casing yangaphandle inamandla amakhulu, ivikelwe ngokugcwele, i-Ultra-lightweight ABS structure.
●Umgomo wokulinganisa: Inzwa ye-infrared engahlakazisi (NDIR)
●Ibanga lokulinganisa: 0-2000ppmv SF6
●Isixazululo: 0.1ppmv
●Ukunemba: ±2%FS
Ngisho nebanga lokulinganisa lingaphezu kuka-5000ppm, ithuluzi ngeke lonakale.
●Iphutha lokuphinda: ≤±1%
●Ukuzwela: 1ppmv
●Isikhathi sokuphendula: ≤10s
●Isikhathi sokutakula: ≤15s
●Ukuzinza: ≤±20ppm, amahora angaphezu kuka-1000
●Imodi yesampula: uhlobo lokumunca iphampu, ukugeleza kufikela ku-1L/min.
●Ukushintsha kukaziro: ≤±1%(FS/ngonyaka)
●Iphutha lomugqa: ≤±1%
●Inani eliphakeme kakhulu lamanje: <700mA
●Amandla amaphakathi: <2W.
●Ukusebenza komoya wokucindezela: 800-1150hPa.
●Umswakama wendawo: 0-95%RH
●Izinga lokushisa lesitoreji: -20°+60℃
●Izinga lokushisa lokusebenza: -20°+50℃
●Ukusebenza kokuswakama: 0-95% (okungafinyeleli)
●I-voltage esebenzayo: 220VAC±10%,50Hz Noma Ibhethri le-Li elakhelwe ngaphakathi, ukusebenza okuqhubekayo amahora angu-6 ngemva kokushajwa okuphelele.
●Ubukhulu: 220×250×120mm
●Isisindo: mayelana ne-2kg
Iyunithi eyinhloko | 1 isethi |
Ishaja | 1 isiqephu |
Ubanjwe ngesandlaphenya | 1 isiqephu |
Ibhande elilwa nokushelela | 1 isiqephu |
Hnoma 600mm | 1 isiqephu |
Umsebenzisi's umhlahlandlela | 1 ikhophi |
Wikhadi le-arranty | 1 ikhophi |